Lithuanian INSC Home Page International Partners Nuclear Plants Contact Us LEI Web Site
INSC Banner

Control system for the RBMK-1500 RELAP5 model


4.2 The Control and Protection System (CPS)

 

The CPS consists of several signals to shut down the fission reaction or reduce the power to a lower level. The CPS Signals and the actuation criteria applicable for the RELAP5 model are summarized below.

 

Fast-Acting Scram (FAS Signal)

 

The FAS Signal is used in especially urgent situations, when a sudden change in reactivity cannot be avoided. The FAS Signal leads to the insertion of 24 fast-acting scram rods (FASR) at 2.5 m/s and 40 shortened absorber rods at a speed of 0.4 m/s, and the remaining 147 rods in 14 s. The actuation signals are developed next [3]. These include;

High pressure in the ACS

Since the ACS is not modeled, the high pressure signal from a LOCA will not be considered.

Instability during start-up

The scope of the current model is for full-power, operational transients. Consequently, these signal will not be considered.

Reactor power level 10% above nominal

The non-dimensional power level is compared to the setpoint power (4155 MW) [2] in Control Variable 520 and a trip is issued if the power exceeds 110% of the setpoint (110% is referenced in [3] ).

Non-dimensionalize the core power coming out of the reactor physics package as

520 CV-520 = P/P0 = (rktpow 0)/4.155e9 W

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20552000

W1(A) ALPHANUMERIC NAME = power

W2(A) CONTROL COMPONENT TYPE = constant

W3(R) SCALING FACTOR = 1.0

For a constant component, this quantity is the constant value. No additional words are entered on this card, and cards 205CCC01 through 205CCC09 or 205CCCC1 through 205CCCC9 are not entered.

130 Is the non-dimensional power > 110%?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601300

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 520

W1(A) and W2(I) represent the current non-dimensional core power

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 1.1

    1. represents 110%

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Manual FAS Signal

The FAS Signal is the combination of the signals defined above and a manual signal.

131 The manual signal will occur when time > 1.e6 s (e.g., never active)?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601310

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W1(A) and W2(I) represent the current transient time

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 1.e6

This is an arbitrarily high user-specified time.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611010

W1(A) TRIP NUMBER = 131

The manual signal will occur when time > 1.e6 s (e.g., never active)

W2(A) OPERATOR = and

W3(A) TRIP NUMBER = 101

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

FAS Signal

The FAS Signal is the combination of the signals defined above.

1130 Is there either a 110% high power signal or a short-term ECCS signal?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611300

W1(I) TRIP NUMBER = 130

110% high power signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1110

Short-term ECCS signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1131 Is there a 110% high power signal, a short-term ECCS signal, or a manual FAS signal?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611310

W1(I) TRIP NUMBER = 1130

110% high power or short-term ECCS signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 131

Manual FAS signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

FAS reactivity

Upon getting a FAS Signal, Table 525 is used to provide the negative reactivity versus time for the insertion of 24 fast-acting scram rods (FASR) at 2.5 m/s, 40 shortened absorber rods at a speed of 0.4 m/s, and the remaining 147 rods in 14 s. The FAS reactivity versus time is obtained from plant data and calculations ([3] for the first 3 s).

521 CV-521 = FAS Reactivity from Table 525

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20552100

W1(A) ALPHANUMERIC NAME = fas_reac

W2(A) CONTROL COMPONENT TYPE = function

Specifies a function component. The function component gets a value from a standard table.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = 0.0

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20552101

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = time 0

Specifies the transient time.

W3(R) TABLE NUMBER = 525

The FAS reactivity table.

525 FAS Reactivity Table

CARD 202TTT00, TABLE TYPE AND MULTIPLIER DATA

Card 20252500

W1(A) TABLE TYPE = reac-t

react-t specifies a table type for reactivity versus time. Although the data in this table does not have to represent reactivity versus time data, it is a common practice to use this option when no units conversion is desired.

W2(I) TRIP NUMBER = 1131

CARD 202TTT01 THROUGH 202TTT99, GENERAL TABLE DATA

Card

Number

Time after Trip

[s]

Reactivity

[$]

20252501

0.0

0.0

20252502

0.5

-0.3

20252503

1.0

-1.0

20252504

1.2

-2.5

20252505

1.5

-2.7

20252506

2.0

-2.8

20252507

2.5

-2.9

20252508

3.0

-3.0

20252509

4.7

-6.8

20252510

7.1

-10.0

20252511

9.5

-12.4

20252512

11.9

-14.3

20252513

14.2

-17.0

 

To eliminate discontinuities if successively higher CPS signals are actuated, the highest negative reactivity from all lower level signals and FAS signal are considered. For example, if an AZ-3 signal is generated and degrades into a FAS signal, the control rod movement already considered in the AZ-3 signal will not be reset back to zero.

522 CV-522 = min( rFAS, rAZ-1, rAZ-3, rAZ-4, and CV-522)

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20552200

W1(A) ALPHANUMERIC NAME = react

W2(A) CONTROL COMPONENT TYPE = stdfnctn

Specifies a function component. The function component gets a value from a standard table.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20552201

W1(A) FUNCTION TYPE = min

W2(A) & W3(I) VARIABLE REQUEST CODE V1 = cntrlvar 521

Specifies the FAS reactivity.

Card 20552202

W1(A) & W2(I) VARIABLE REQUEST CODE V2 = cntrlvar 526

Specifies the AZ-1 reactivity.

Card 20552203

W1(A) & W2(I) VARIABLE REQUEST CODE V3 = cntrlvar 562

Specifies the AZ-3 and AZ-4 reactivity.

Card 20552204

W1(A) & W2(I) VARIABLE REQUEST CODE V4 = cntrlvar 522

Specifies the previous timestep minimum value.

 

Next, the minimum reactivity developed by the CPS signals is multiplied by a "trip unit" signifying the occurrence of either a FAS or AZ-1 signal.

523 CV-523 = tripunit (FAS or AZ-1 signal)

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20552300

W1(A) ALPHANUMERIC NAME = fas_az1

W2(A) CONTROL COMPONENT TYPE = tripunit

Specifies a trip unit function.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20552301

W1(A) TRIP NUMBER = 1253

AZ-1 or a FAS signal

 

525 CV-525 = min (rFAS, rAZ-1 , rAZ-3, rAZ-4 )* tripunit(FAS or AZ-1)

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20552500

W1(A) ALPHANUMERIC NAME = fas_az1

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiply function.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20552501

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = cntrlvar 522

Card 20552502

W1(A) & W2(I) VARIABLE REQUEST CODE V2 = cntrlvar 523

Specifies the FAS or AZ-1 trip has occurred.

 

Emergency Protection 1 (AZ-1) Signal

This is a normal shutting down of the chain reaction. The AZ-1 Signal leads to the insertion of 24 FASR in 6-8 s and the remaining rods as in the FAS. The actuation signals [ ] are developed next.

Turbine Trip or Loss of Load

An AZ-1 Signal is initiated when both turbines trip or lose their load (or one turbine trip or loss of load to one turbine if only one turbine is operating). The turbine is not simulated in the RELAP5 model. Furthermore, the RBMK model assumes that both turbines are operating. Consequently, this trip will be monitored by a closure of both turbine control valves. Trip 140 monitors the RHS of the reactor while Trip 141 monitors the LHS of the reactor.

140 Is the LHS TCV flow area < 5.e-2 (e.g., closed)?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601400

W1(A) VARIABLE CODE = vlvarea

W2(I) PARAMETER = 195

W1(A) and W2(I) represent the non-dimensional valve area for the RHS Turbine Control Valve

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 5.e-2

Arbitrarily small valve opening.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

141 Is the RHS TCV flow area < 5.e-2 (e.g., closed)?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601410

W1(A) VARIABLE CODE = vlvarea

W2(I) PARAMETER = 595

W1(A) and W2(I) represent the non-dimensional valve area for the RHS Turbine Control Valve

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 5.e-2

Arbitrarily small valve opening.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1140 Are either the RHS and the LHS TCV closed?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611400

W1(I) TRIP NUMBER = 140

LHS TCV closure signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 141

RHS TCV closure signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

Main Coolant Pump (MCP) Trip

An AZ-1 Signal is activated when two out of the three MCPs trip off. Since all three pumps are lumped together on the LHS, an AZ-1 Signal is generated when the lumped pump trips. On the RHS, two out of three logic is used to evaluate whether the two pumps are tripped. It is not known how a MCP trip is monitored at the plant. For the RELAP5 model, failure of the main recirculation pumps will be monitored through the pump motor torque. Since the pump motor torque is not normally available as a minor edit variable, it must also be designated through the expanded plot variables. The culmination of the logic is Logical Trip 1155.

CARD 2080XXXX, EXPANDED PLOT VARIABLE REQUEST CARD

Card 20800110

W1(I) & W2(A) EXPANDED VARIABLE REQUEST CODE = pmpmt 135

Requests the motor torque from LHS Pumps (Component 135)

Card 20800111

W1(I) & W2(A) EXPANDED VARIABLE REQUEST CODE = pmpmt 535

Requests the motor torque from RHS Pump (Component 535)

Card 20800112

W1(I) & W2(A) EXPANDED VARIABLE REQUEST CODE = pmpmt 635

Requests the motor torque from RHS Pump (Component 635)

Card 20800113

W1(I) & W2(A) EXPANDED VARIABLE REQUEST CODE = pmpmt 835

Requests the motor torque from RHS Pump (Component 835)

 

150 CV-150 = LHS MCP motor torque

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20515000

W1(A) ALPHANUMERIC NAME = torque

W2(A) CONTROL COMPONENT TYPE = sum

Specifies a sum component.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = 130264.

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20515001

W1(R) ADDITIVE CONSTANT = 0.0

No additive constant.

W2(R) GAIN FOR V1 = 1.0

W3(A) & W4(I) VARIABLE REQUEST CODE V1 = pmpmt 135

Motor torque for the LHS MCPs

 

151 CV-151 = RHS MCP motor torque

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20515100

W1(A) ALPHANUMERIC NAME = torque

W2(A) CONTROL COMPONENT TYPE = sum

Specifies a sum component.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = 43229.6

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20515101

W1(R) ADDITIVE CONSTANT = 0.0

No additive constant.

W2(R) GAIN FOR V1 = 1.0

W3(A) & W4(I) VARIABLE REQUEST CODE V1 = pmpmt 535

Motor torque for the RHS MCP

 

152 CV-152 = RHS MCP motor torque

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20515200

W1(A) ALPHANUMERIC NAME = torque

W2(A) CONTROL COMPONENT TYPE = sum

Specifies a sum component.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = 43229.6

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20515201

W1(R) ADDITIVE CONSTANT = 0.0

No additive constant.

W2(R) GAIN FOR V1 = 1.0

W3(A) & W4(I) VARIABLE REQUEST CODE V1 = pmpmt 635

Motor torque for the RHS MCP

 

153 CV-153 = RHS MCP motor torque

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20515300

W1(A) ALPHANUMERIC NAME = torque

W2(A) CONTROL COMPONENT TYPE = sum

Specifies a sum component.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = 43229.6

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20515301

W1(R) ADDITIVE CONSTANT = 0.0

No additive constant.

W2(R) GAIN FOR V1 = 1.0

W3(A) & W4(I) VARIABLE REQUEST CODE V1 = pmpmt 835

Motor torque for the RHS MCP

 

150 Is the LHS pump motor torque > 1.e-3 N-m (e.g., the motor has tripped)

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601500

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 150

W1(A) and W2(I) represent the LHS MCP motor torque

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 1.e-3

Arbitrarily small pump motor torque.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

151 Is the RHS pump motor torque > 1.e-3 N-m (e.g., the motor has tripped)

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601510

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 151

W1(A) and W2(I) represent the RHS MCP motor torque

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 1.e-3

Arbitrarily small pump motor torque.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

152 Is the RHS pump motor torque > 1.e-3 N-m (e.g., the motor has tripped)

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601520

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 152

W1(A) and W2(I) represent the RHS MCP motor torque

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 1.e-3

Arbitrarily small pump motor torque.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

153 Is the RHS pump motor torque > 1.e-3 N-m (e.g., the motor has tripped)

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601530

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 153

W1(A) and W2(I) represent the RHS MCP motor torque

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 1.e-3

Arbitrarily small pump motor torque.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Next, all possible combinations of 2 out of 3 pumps tripped are evaluated.

 

1150 Have RHS 1 and RHS 2 pumps tripped?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611500

W1(I) TRIP NUMBER = 151

RHS 1 pump motor has tripped off

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 152

RHS 2 pump motor has tripped off

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1151 Have RHS 1 and RHS 3 pumps tripped?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611510

W1(I) TRIP NUMBER = 151

RHS 1 pump motor has tripped off

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 153

RHS 3 pump motor has tripped off

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1152 Have RHS 2 and RHS 3 pumps tripped?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611520

W1(I) TRIP NUMBER = 152

RHS 2 pump motor has tripped off

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 153

RHS 3 pump motor has tripped off

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1153 Have the LHS or RHS 1 and RHS 2 pumps tripped?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611530

W1(I) TRIP NUMBER = 150

LHS pump motor has tripped off

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1150

RHS 1 and RHS 2 pump motors have tripped off

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1154 Have the RHS 1 and RHS 3 or RHS 2 and RHS 3 pumps tripped?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611540

W1(I) TRIP NUMBER = 1151

RHS 1 and RHS 3 pump motor have tripped off

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1152

RHS 2 and RHS 3 pump motor have tripped off

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1155 Have the 2/3 pumps tripped on either the LHS or the RHS? This trip indicates whether 2 of 3 MCPs have tripped on either side of the reactor.

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611550

W1(I) TRIP NUMBER = 1153

LHS or RHS 1 and RHS 2 pump motors have tripped off

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1154

RHS 1 and RHS 3 or RHS 2 and RHS 3 pump motors have tripped off

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

Low flow in MCPs

Low flow (< 5,000 m3/hr) in 2 out of 3 MCPs will be monitored by examining the average flowrate through the pumps. Control Variables are used to evaluate the volumetric flow near the pumps. Logical Trips are used to evaluate whether 2 out of 3 pumps are simultaneously at low flow conditions. The culmination of the logic is Logical Trip 1165.

 

535 CV-535 = v A (3600 s/hr) = [m3/hr]

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20553500

W1(A) ALPHANUMERIC NAME = lhs_mcp

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier component.

W3(R) SCALING FACTOR = 3600.0

Converts m3/s to m3/hr.

W4(R) INITIAL VALUE = 22941.06

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20553501

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = velf 135010000

Specifies the cell center liquid velocity in the lhs MCP.

W3(A) & W4(I) VARIABLE REQUEST CODE V2 = avol 135010000

Specifies the cell flow area in the lhs MCP.

 

536 CV-536 = v A (3600 s/hr) = [m3/hr]

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20553600

W1(A) ALPHANUMERIC NAME = rhs_mcp1

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier component.

W3(R) SCALING FACTOR = 3600.0

Converts m3/s to m3/hr.

W4(R) INITIAL VALUE = 7643.9

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20553601

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = velf 535010000

Specifies the cell center liquid velocity in the rhs 1 MCP.

W3(A) & W4(I) VARIABLE REQUEST CODE V2 = avol 535010000

Specifies the cell flow area in the rhs 1 MCP.

 

537 CV-537 = v A (3600 s/hr) = [m3/hr]

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20553700

W1(A) ALPHANUMERIC NAME = rhs_mcp2

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier component.

W3(R) SCALING FACTOR = 3600.0

Converts m3/s to m3/hr.

W4(R) INITIAL VALUE = 7643.9

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20553701

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = velf 635010000

Specifies the cell center liquid velocity in the rhs 2 MCP.

W3(A) & W4(I) VARIABLE REQUEST CODE V2 = avol 635010000

Specifies the cell flow area in the rhs 2 MCP.

538 CV-537 =v A (3600 s/hr) = [m3/hr]

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20553800

W1(A) ALPHANUMERIC NAME = rhs_mcp3

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier component.

W3(R) SCALING FACTOR = 3600.0

Converts m3/s to m3/hr.

W4(R) INITIAL VALUE = 7643.9

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20553801

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = velf 835010000

Specifies the cell center liquid velocity in the rhs 3 MCP.

W3(A) & W4(I) VARIABLE REQUEST CODE V2 = avol 835010000

Specifies the cell flow area in the rhs 3 MCP.

 

Next, it is determined whether the flow through any MCP is < 5000 m3/hr

160 Is the sum of the flows through the three LHS MCPs < 15,000 m3/hr (3*5,000 m3/hr)? Since the lumped LHS MCP model represents three working MCPs, it will be assumed that the average flow through all three MCPs must drop below 15,000 m3/hr.

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601600

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 535

W1(A) and W2(I) represent the flow through the 3 lumped LHS MCPs

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 15000

Since three MCPs are considered, the flow is compared to 15,000 m3/hr or 3*5000 m3/hr

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

161 Is the flow through RHS 1 MCP < 5000 m3/hr?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601610

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 536

W1(A) and W2(I) represent the flow through the RHS 1 MCP

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 5000.0

The flow through the RHS 1 MCP is compared to 5000 m3/hr

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

162 Is the flow through RHS 2 MCP < 5000 m3/hr?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601620

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 537

W1(A) and W2(I) represent the flow through the RHS 2 MCP

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 5000

The flow through the RHS 2 MCP is compared to 5000 m3/hr

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

163 Is the flow through RHS 3 MCP < 5000 m3/hr?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601630

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 538

W1(A) and W2(I) represent the flow through the RHS 3 MCP

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 5000

The flow through the RHS 3 MCP is compared to 5000 m3/hr

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Finally, 2 out of 3 logic is used to evaluate whether 2 out of 3 MCPs on either side of the reactor have low flow signals.

1160 Do the RHS 1 and RHS 2 pumps have low flow signals?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611600

W1(I) TRIP NUMBER = 161

RHS 1 MCP has a low flow signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 162

RHS 2 MCP has a low flow signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1161 Do the RHS 1 and RHS 3 pumps have low flow signals?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611610

W1(I) TRIP NUMBER = 161

RHS 1 MCP has a low flow signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 163

RHS 3 MCP has a low flow signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1162 Do the RHS 2 and RHS 3 pumps have low flow signals?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611620

W1(I) TRIP NUMBER = 162

RHS 2 MCP has a low flow signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 163

RHS 3 MCP has a low flow signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1163 Do the LHS MCPs or RHS 1 and RHS 2 pumps have low flow signals?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611630

W1(I) TRIP NUMBER = 160

The LHS MCPs have low flow signals

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 1160

RHS 1 and RHS 2 MCP have low flow signals

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1164 Do the RHS 1 and RHS 3 MCPs or RHS 2 and RHS 3 pumps have low flow signals?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611640

W1(I) TRIP NUMBER = 1161

RHS 1 and RHS 3 MCP have low flow signals

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 1162

RHS 2 and RHS 3 MCP have low flow signals

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1165 Are there 2 out of 3 MCPs on either side of the reactor with low flow signals?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611650

W1(I) TRIP NUMBER = 1163

LHS MCPs or RHS 1 and RHS 2 MCP have a low flow signals

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 1164

RHS 2 and RHS 3 MCP or RHS 1 and RHS 3 MCP have a low flow signals

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Low feedwater flow

Low feedwater flow (< 50%) relative to setpoint for the current power will be monitored by examining the

non-dimensional flowrate through the feedwater inlet. The culmination of the logic is Logical Trip 1167.

530 CV-530 = /0 = (mflowj 107000000)/(1074 kg/s)

where,

mflowj 107000000 LHS feedwater flow

1074 kg/s Steady state feedwater flow to the LHS steam drums at 4155 MW.

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20553000

W1(A) ALPHANUMERIC NAME = lhs_fw

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier component. The feedwater flow is scaled according to W3, no multiplication is performed because only one variable request code is entered.

W3(R) SCALING FACTOR = 9.306x10-4

1/1074 kg/s to non-dimensionalize the LHS feedwater flow.

W4(R) INITIAL VALUE = 1.040317

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20553001

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = mflowj 107000000

Specifies the LHS feedwater flow

 

531 CV-531 = /0 = (mflowj 507000000)/(537 kg/s)

where,

mflowj 507000000 RHS 1 feedwater flow

537 kg/s Steady state feedwater flow to the RHS 1 steam drum at 4155 MW.

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20553100

W1(A) ALPHANUMERIC NAME = rhs_fw1

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier component. The feedwater flow is scaled according to W3, no multiplication is performed because only one variable request code is entered.

W3(R) SCALING FACTOR = 1.861x10-3

1/532 kg/s to non-dimensionalize the RHS 1 feedwater flow.

W4(R) INITIAL VALUE = 2.080184

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20553101

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = mflowj 507000000

Specifies the RHS 2 feedwater flow

 

533 CV-533 = 50% of the mfw demand flow ~ 50% * P/P0

where,

P/P0 Load demand signal from the feedwater controllers

 

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20553300

W1(A) ALPHANUMERIC NAME = dmd_mfw

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier component. The feedwater flow is scaled according to W3, no multiplication is performed because only one variable request code is entered.

W3(R) SCALING FACTOR = 0.5

The low feedwater signal is based on 50% of the main feedwater demand signal.

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20553301

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = cntrlvar 200

Load demand signal from the drum level control system

 

Next, the flow feedwater flow signals for the LHS and RHS are determined.

Low feedwater flow

Low feedwater flow (< 75%) relative to setpoint for the nominal power will be monitored by examining the average flowrate through the pump. 75% of the feedwater demand flow is estimated by taking the non-dimensional load signal from the steam drum controllers and multiplying it by 0.75. The culmination of the logic is Logical Trip 1250.

534 CV-534 = 75% of the mfw demand flow ~ 75% * P/P0

where,

P/P0 Load demand signal from the feedwater controllers

 

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20553400

W1(A) ALPHANUMERIC NAME = dmd_mfw

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier component. The feedwater flow is scaled according to W3, no multiplication is performed because only one variable request code is entered.

W3(R) SCALING FACTOR = 0.75

The low feedwater signal is based on 75% of the main feedwater demand signal.

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20553401

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = cntrlvar 200

Load demand signal from the drum level control system

 

166 Is the LHS feedwater flow < 50% of the demand flow?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601660

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 530

W1(A) and W2(I) LHS feedwater flow

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = cntrlvar

W5(I) PARAMETER = 533

Comparison to 50% of the feedwater demand flow

W6(R) ADDITIVE CONSTANT = 0.0

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

167 Is the RHS 1 feedwater flow < 50% of the demand flow?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601670

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 531

W1(A) and W2(I) RHS 1 feedwater flow

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = cntrlvar

W5(I) PARAMETER = 533

Comparison to 50% of the feedwater demand flow

W6(R) ADDITIVE CONSTANT = 0.0

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1167 Is there a low LHS feedwater signal or a low RHS 1 feedwater signal?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611670

W1(I) TRIP NUMBER = 166

Low LHS feedwater signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 167

Low RHS 1 feedwater signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

High or Low Water Level in Steam Separator Drums

High (+250 mm) and low (-1000 mm) water levels relative the 0 mm level will be monitored by examining the steam drum water levels. The 0 mm level is 295 mm above the geometric center (see Section 4.3). The culmination of the high and low level logic is Logical Trip 1174.

First, the high steam drum signals are evaluated.

 

170 Is the LHS steam drum level > 250 mm?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601700

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 212

W1(A) and W2(I) represent the collapsed steam drum level in the LHS

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 250.0

Current collapsed level is compared to a high level setting of 250 mm.

W7(A) LATCH INDICATOR = n

Do not latch to permit momentary high level signals to be ignored.

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

171 Is the RHS 1 steam drum level > 250 mm?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601710

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 222

W1(A) and W2(I) represent the collapsed steam drum level in the RHS 1

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 250.0

Current collapsed level is compared to a high level setting of 250 mm.

W7(A) LATCH INDICATOR = n

Do not latch to permit momentary high level signals to be ignored.

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

173 Is the LHS steam drum level < -1000 mm?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601730

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 212

W1(A) and W2(I) represent the collapsed steam drum level in the LHS

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = -1000.0

Current collapsed level is compared to a low level setting of -1000 mm.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

174 Is the RHS 1 steam drum level < -1000 mm?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601740

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 222

W1(A) and W2(I) represent the collapsed steam drum level in the RHS 1

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = -1000.0

Current collapsed level is compared to a low level setting of -1000 mm.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Finally, the high and low level signals from the LHS and RHS are combined.

1171 Is there a high level signal from either the LHS or the RHS?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611710

W1(I) TRIP NUMBER = 171

High steam drum level from RHS

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 170

High steam drum level from LHS

W4(A) LATCH INDICATOR = n

Do not latch to permit momentary high level signals to be ignored.

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1173 Is there a low level signal from either the LHS or the RHS?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611730

W1(I) TRIP NUMBER = 174

Low steam drum level from RHS

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 173

Low steam drum level from LHS

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1174 Is there a low or high level signal from either the LHS or the RHS?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611740

W1(I) TRIP NUMBER = 1171

High steam drum level from the LHS or RHS

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1173

Low steam drum level from LHS or RHS

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

High Steam Drum Pressure

High steam drum pressure (> 7.36 MPa) signal will be monitored by examining the steam drum pressure. The culmination of the high pressure logic is Logical Trip 1181.

180 Is LHS steam drum pressure > 7.36 MPa?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601800

W1(A) VARIABLE CODE = p

W2(I) PARAMETER = 100010000

W1(A) and W2(I) represent the LHS steam drum pressure

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 7.36e6

High pressure setpoint of 7.36 MPa

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

181 Is RHS 1 steam drum pressure > 7.36 MPa?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601810

W1(A) VARIABLE CODE = p

W2(I) PARAMETER = 500010000

W1(A) and W2(I) represent the RHS 1 steam drum pressure

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 7.36e6

High pressure setpoint of 7.36 MPa

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Next, the high pressure signals from the LHS and RHS are combined together.

1181 Is there a high pressure signal from either the LHS or the RHS steam drums?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611810

W1(I) TRIP NUMBER = 180

High pressure signal from the LHS steam drum

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 181

High pressure signal from the RHS 1 steam drum

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

Loss of voltage in all 6 kV lines

The loss of the 6 kV lines is not modeled explicitly in the RELAP model. Trip 102, which signifies a loss-of-offsite power, will be used as the loss of the 6 kV lines. Consistent with the Station Blackout Analysis [ ], a 2 s delay is used between the loss of offsite power and the AZ-1 signal.

185 Has 2 s elapsed since the loss-of-offsite power?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20601850

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W1(A) and W2(I) represent the transient time

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = timeof

W5(I) PARAMETER = 102

W6(R) ADDITIVE CONSTANT = 2

A 2 s delay from the loss-of-offsite power is included to be consistent with the Station Blackout analysis.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

Signals of systems not modeled

The following AZ-1 Signals will not be monitored because the systems are not modeled.

• Neutron flux exceeds the trip limits in three or more LPLP zones (RELAP5 uses a point kinetics model and does not model any spatial dependency). A 110% over-power condition is considered in the FAS trip logic.

• For the case of the station blackout, the loss of the 6 kV lines is modeled with loss-of-offsite power (Trip 102).

• Reduction of the water level in the top storage tank of the control rod cooling circuit (CRCC).

• Reduction of the water flow in the CRCC distribution header to 255 kg/s.

• Reduction of the over-pressure in the CRCC distribution header to 150 kPa.

• Decrease in the ECCS top tanks to 15% below nominal.

• High gage pressure 2 kPa in the feedwater and the steam pipe compartments.

Manual AZ-1 Signal

The AZ-1 Signal is the culmination of the signals listed above. It also includes a manual signal (Trip 190).

190 Manual AZ-1 Signal will occur when time > 1.e6 s (e.g., never active)?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CAR

Card 20601900

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W1(A) and W2(I) represent the current transient time

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 1.e

This is an arbitrarily high user-specified time.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

AZ-1 Signa

The AZ-1 Signal is the culmination of the signals listed above

1190 Is there a turbine trip signal or a MCP trip signal?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611900

W1(I) TRIP NUMBER = 1140

Turbine trip signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1155

MCP trip signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1191 Have any of the following signals occurred; Turbine trip, MCP trip, Low MCP flow?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611910

W1(I) TRIP NUMBER = 1190

Turbine trip or MCP trip signals

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1165

Low MCP flow signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1192 Have any of the following signals occurred; Turbine trip, MCP trip, Low MCP flow, and Low feedwater flow?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611920

W1(I) TRIP NUMBER = 1191

Turbine trip, MCP trip, or low MCP flow signals

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1167

Low feedwater signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1193 Have any of the following signals occurred; Turbine trip, MCP trip, Low MCP flow, Low feedwater flow, High or low steam drum level?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611930

W1(I) TRIP NUMBER = 1192

Turbine trip, MCP trip, low MCP flow, or low feedwater flow signals

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1174

High or Low steam drum level signals

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1194 Have any of the following signals occurred; Turbine trip, MCP trip, Low MCP flow, Low feedwater flow, High or low steam drum level, High steam drum pressure?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611940

W1(I) TRIP NUMBER = 1193

Turbine trip, MCP trip, low MCP flow, low feedwater flow, or high or low steam drum level signals

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1181

High steam drum pressure signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1195 Have any of the following signals occurred; Turbine trip, MCP trip, Low MCP flow, Low feedwater flow, High or low steam drum level, High steam drum pressure, Low of 6 kV bus (Trip 102 + 2 s delay)?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611950

W1(I) TRIP NUMBER = 1194

Turbine trip, MCP trip, low MCP flow, low feedwater flow, high or low steam drum level, or high steam drum pressure signals

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 185

Low of 6 kV bus (Trip 102 + 2 s delay)

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1196 Have any of the following signals occurred; Turbine trip, MCP trip, Low MCP flow, Low feedwater flow, High or low steam drum level, High steam drum pressure, Low of 6 kV bus (Trip 102 + 2 s delay), or Manual AZ-1 signal?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611960

W1(I) TRIP NUMBER = 1195

Turbine trip, MCP trip, low MCP flow, low feedwater flow, high or low steam drum level, high steam drum pressure, or low of 6 kV bus signals

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 190

Manual AZ-1 signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Logic is added to prevent a simultaneous AZ-1 and FAS signal. Since the control logic inserts negative reactivity most quickly during an FAS signal, a AZ-1 signal is precluded from occurring when an FAS signal is active.

1196 Have any of the following signals occurred; Turbine trip, MCP trip, Low MCP flow, Low feedwater flow, High or low steam drum level, High steam drum pressure, Low of 6 kV bus (Trip 102 + 2 s delay), Manual AZ-1 signal, and an FAS signal has not occurred

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611970

W1(I) TRIP NUMBER = 1196

Turbine trip, MCP trip, low MCP flow, low feedwater flow, high or low steam drum level, high steam drum pressure, low of 6 kV bus, or a manual AZ-1 signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -1131

No FAS signal

W4(A) LATCH INDICATOR = n

Not latched to permit FAS to over-ride.

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

AZ-1 Reactivity

Upon getting an AZ-1 Signal, Table 535 is read to provide the negative reactivity versus time for inserting 24 FASR in 6-8 s and the remaining rods as in the FAS. The AZ-1 reactivity versus time is obtained from plant data .

 

535 CV-535 = AZ-1 Reactivity from Table 535

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20552600

W1(A) ALPHANUMERIC NAME = az1_reac

W2(A) CONTROL COMPONENT TYPE = function

Specifies a function component. The function component gets a value from a standard table.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20552601

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = time 0

Specifies the transient time.

W3(R) TABLE NUMBER = 535

The AZ-1 reactivity table.

 

535 AZ-1 Reactivity Table

CARD 202TTT00, TABLE TYPE AND MULTIPLIER DATA

Card 20253500

W1(A) TABLE TYPE = reac-t

react-t specifies a table type for reactivity versus time. Although the data in this table does not have to represent reactivity versus time data, it is a common practice to use this option when no units conversion is desired.

W2(I) TRIP NUMBER = 1197

CARD 202TTT01 THROUGH 202TTT99, GENERAL TABLE DATA

Card

Number

Time after Trip

[s]

Reactivity

[$]

20253501

0.0

0.0

20253502

1.0

-0.9

20253503

2.0

-1.8

20253504

2.4

-2.3

20253505

4.7

-6.8

20253506

7.1

-10.0

20253507

9.5

-12.4

20253508

11.9

-14.3

20253509

14.2

-17.0

 

Emergency Protection 3 (AZ-3) Signal

 

The AZ-3 Signal causes a reduction in the total power to 50% of nominal. The power is reduced at a rate of 2%/s and takes 25 s to reach the 50% power level [ ]. The following signals from the RELAP5 model will be used to initiate the AZ-3 signal.

 

Turbine Trip or Loss of Load

An AZ-3 Signal is initiated when one turbine trips or loss load. The turbine is not simulated in the RELAP5 model. Furthermore, the model assumes that both turbines are operating. Consequently, this trip will be monitored by a closure of one turbine control valves. Trip 1112 monitors the exclusive closure of either the RHS or LHS turbine control valve.

 

1142 Is either the LHS TCV or the RHS TCV (but not both) closed?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20611420

W1(I) TRIP NUMBER = 140

Closure signal for the LHS TCV

W2(A) OPERATOR = xor

RELAP5 argument for an exclusive comparison

W3(I) TRIP NUMBER = 141

Closure signal for the RHS TCV

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Signals of systems not modeled

The following AZ-3 Signal will not be monitored because the system is not modeled.

• AZ-6 Signal while operating at 50% to 100%. The AZ-6 Signal is at least two SLP-R neutron flux sensors in a single Local Power Level Protection (LPLP) zone exceeds the power setpoint (RELAP5 uses a point kinetics model and does not model spatial dependence).

Manual AZ-3 Signal

200 A manual AZ-3 signal will occur when time > 1.e6 s (e.g., never active)?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20602000

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W1(A) and W2(I) represent the current transient time

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 1.e6

This is an arbitrarily high user-specified time.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

AZ-3 Signal

The AZ-3 signal is the culmination of all the signals listed above. The trip logic to combine those signals is listed below.

1200 Have either of the TCVs closed or is there a manual AZ-3 signal?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612000

W1(I) TRIP NUMBER = 1142

Closure of either the LHS or RHS TCV

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 200

Manual AZ-3 signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

The AZ-3 signal is the least severe CPS signal considered. Logic is added to prevent a AZ-3 power reduction signal if an FAS, AZ-1, or AZ-4 signal has occurred.

1201 Has either a FAS or AZ-1 signal occurred?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612010

W1(I) TRIP NUMBER = 1131

FAS signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1197

AZ-1 signal

W4(A) LATCH INDICATOR = n

Not latched to permit other protection signals to over-ride.

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1203 Is there a AZ-3 signal and a FAS or a AZ-1 signal not occurred?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612030

W1(I) TRIP NUMBER = -1201

Not a FAS or a AZ-1 signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 1200

AZ-3 signal

W4(A) LATCH INDICATOR = n

Not latched to permit other protection signals to over-ride.

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

Emergency Protection 4 (AZ-4) Signal

The AZ-4 Signal causes a reduction in the total power to 60% of nominal. The power is reduced at a rate of 2%/s and takes 20 s to reach the 60% power level [3,4]. The following signals from the RELAP5 model will be used to initiate the various levels of CPS.

One MCP Trip

An AZ-3 Signal occurs when one out of the three MCPs trip off. Since all three pumps are lumped together on the LHS, only three pumps can trip. The AZ-1 MCP pump trip signal already addresses the situation of all three pumps tripping. Consequently, a LHS pump trip will not be modeled here. On the RHS, one out of three logic will be used to evaluate whether the two pumps are tripped. The culmination of the logic is Logical Trip 1217.

1210 Are RHS 1 and RHS 2 MCPs operating?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612100

W1(I) TRIP NUMBER = -151

RHS 1 pump is not tripped

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -152

RHS 2 pump is not tripped

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1211 Are RHS 1 and RHS 3 MCPs operating?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612110

W1(I) TRIP NUMBER = -151

RHS 1 pump is operating

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -153

RHS 3 pump is operating

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1212 Are RHS 2 and RHS 3 MCPs operating?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612120

W1(I) TRIP NUMBER = -152

RHS 2 pump is operating

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -153

RHS 3 pump is operating

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1213 Is RHS 1 tripped with RHS 2 and RHS 3 operating?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612130

W1(I) TRIP NUMBER = 151

RHS 1 pump is tripped

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 1212

RHS 2 and RHS 3 pump are operating

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1214 Is RHS 2 tripped with RHS 1 and RHS 3 operating?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612140

W1(I) TRIP NUMBER = 152

RHS 2 pump is tripped

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 1211

RHS 1 and RHS 3 pump are operating

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1215 Is RHS 3 tripped with RHS 1 and RHS 2 operating?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612150

W1(I) TRIP NUMBER = 153

RHS 3 pump is tripped

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = 1210

RHS 1 and RHS 2 pump are operating

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1216 Is RHS 1 tripped with RHS 2 and RHS 3 operating or is RHS 2 tripped with RHS 1 and RHS 3 operating?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612160

W1(I) TRIP NUMBER = 1213

RHS 1 tripped with RHS 2 and RHS 3 operating

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1214

RHS 2 tripped with RHS 1 and RHS 3 operating

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1217 Is RHS 1 tripped with RHS 2 and RHS 3 operating is RHS 2 tripped with RHS 1 and RHS 3 operating, or is RHS 3 tripped with RHS 1 and RHS 2 operating?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612170

W1(I) TRIP NUMBER = 1216

RHS 1 tripped with RHS 2 and RHS 3 operating or RHS 2 tripped with RHS 1 and RHS 3 operating

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1215

RHS 3 tripped with RHS 1 and RHS 2 operating

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

220 Is the LHS feedwater flow less than 75% of the feedwater demand?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20602200

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 530

W1(A) and W2(I) represent the non-dimensional LHS feedwater flow, a value of 1 is the nominal LHS feedwater flow at 4155 MW.

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = cntrlvar

W5(I) PARAMETER = 534

W1(A) and W2(I) represent 75% of the feedwater demand flow

W6(R) ADDITIVE CONSTANT = 0.0

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

221 Is the RHS 1 feedwater flow less than 75% of the feedwater demand?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20602210

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 531

W1(A) and W2(I) represent the non-dimensional RHS 1 feedwater flow, a value of 1 is the nominal RHS 1 feedwater flow at 4155 MW.

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = cntrlvar

W5(I) PARAMETER = 534

W1(A) and W2(I) represent 75% of the feedwater demand flow

W6(R) ADDITIVE CONSTANT = 0.0

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

222 Is the RHS 2 feedwater flow less than 75% of the feedwater demand?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20602220

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 531

W1(A) and W2(I) represent the non-dimensional RHS 1 feedwater flow, a value of 1 is the nominal RHS 1 feedwater flow at 4155 MW.

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = cntrlvar

W5(I) PARAMETER = 534

W1(A) and W2(I) represent 75% of the feedwater demand flow

W6(R) ADDITIVE CONSTANT = 0.0

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1220 Is either the RHS 1 or the RHS 2 feedwater flow less than 75% of the feedwater demand flow?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612200

W1(I) TRIP NUMBER = 221

Low (< 75%) RHS 1 feedwater flow signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 222

Low (< 75%) RHS 2 feedwater flow signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1221 Is either the LHS or the RHS feedwater flow less than 75% of the feedwater demand flow?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612210

W1(I) TRIP NUMBER = 220

Low (< 75%) LHS feedwater flow signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1220

Low (< 75%) RHS 1 or RHS 2 feedwater flow signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

Low Water Level in Steam Separator Drums

Low (-500 mm) water level relative the 0 mm level will be monitored by examining the steam drum water levels . The 0 mm level is 295 mm above the geometric center (see Section 4.3). The culmination of this logic is Trip 1231.

230 Is the LHS steam drum level less than -500 mm?

 

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20602300

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 212

W1(A) and W2(I) represent the LHS steam drum level signal.

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = -500 mm

Low level signal is at -500 mm

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

231 Is the RHS 1 steam drum level less than -500 mm?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20602310

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 222

W1(A) and W2(I) represent the RHS 1 steam drum level signal.

W3(A) RELATIONSHIP = lt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = -500 mm

Low level signal is at -500 mm

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1231 Are the LHS or the RHS steam drum levels less than -500 mm?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612310

W1(I) TRIP NUMBER = 231

Low level (-500 mm) signals from the RHS 1 and RHS 2 steam drums

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 230

Low level (-500 mm) signal from the LHS steam drum

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

High Water Level in Steam Separator Drums

High (+100 mm) water level relative the 0 mm level will be monitored by examining the steam drum water levels . The 0 mm level is 295 mm above the geometric center (see Section 4.3). The culmination of this logic is Trip 1231.

233 Is the LHS steam drum level greater than 100 mm?

 

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20602330

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 212

W1(A) and W2(I) represent the LHS steam drum level signal.

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 100 mm

High level signal is at 100 mm

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

234 Is the RHS 1 steam drum level greater than 100 mm?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20602340

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 222

W1(A) and W2(I) represent the RHS 1 steam drum level signal.

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = +100 mm

High level signal is at +100 mm

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1233 Are the LHS or the RHS 1 steam drum level greater than 100 mm?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612330

W1(I) TRIP NUMBER = 233

High level (100 mm) signal from the LHS steam drum

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 234

High level (100 mm) signal from the RHS 1 steam drum

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

High or Low Water Level in Steam Separator Drums

The high (+100 mm) and low (-500 mm) water level signals are combined into a signal level signal in this logical trip.

1234 Are the LHS or the RHS steam drum levels greater than 100 mm or less than -500 mm?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612340

W1(I) TRIP NUMBER = 1233

High level (100 mm) signals

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1231

Low level (-500 mm) signals

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Low flow in MCPs

Low flow (< 5000 m3/hr) in any of the MCPs will be monitored by examining the average flowrate through the pump. Since the LHS includes three lumped pumps and low flow condition was already sensed for the AZ-1 Signal, a low flow signal will not be calculated for the LHS. The culmination of the logic is Logical Trip 1141.

1240 Is the RHS 1 or RHS 2 MCP flow < 5000 m3/hr?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612400

W1(I) TRIP NUMBER = 161

RHS 1 low MCP flow signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 162

RHS 2 low MCP flow signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1241 Is the RHS 1, RHS 2, or RHS 3 MCP flow < 5000 m3/hr?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612410

W1(I) TRIP NUMBER = 1240

RHS 1 or RHS 2 low MCP flow signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 163

RHS 3 low MCP flow signal

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

Signals of systems not modeled

The following AZ-4 Signals will not be monitored because the systems are not modeled.

• AZ-6 Signal while operating at 50% to 100%. The AZ-6 Signal is at least two SLP-R neutron flux sensors in a single Local Power Level Protection (LPLP) zone exceeds the power setpoint (RELAP5 uses a point kinetics model and has not spatial dependency).

Manual AZ-4 Signal

250 The manual AZ-4 signal will occur when time > 1.e6 s (e.g., never active)?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20602500

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W1(A) and W2(I) represent the current transient time

W3(A) RELATIONSHIP = gt

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 1.e6

This is an arbitrarily high user specified time.

W7(A) LATCH INDICATOR = l

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

AZ-4 Signal

The AZ-4 Signal is the culmination of the signals listed above.

1250 Have 1 out of 3 of the RHS MCPs tripped or is there low (< 75%) feedwater flow?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612500

W1(I) TRIP NUMBER = 1217

1 out of 3 MCP trip

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1221

Low (< 75%) feedwater flow

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1251 Have any of the following signals occurred; 1 out of 3 of the RHS MCPs tripped; Low (< 75%) feedwater flow; or Low or High (< -500 mm and 100 mm) steam drum level?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612510

W1(I) TRIP NUMBER = 1250

1 out of 3 MCP trip or low (< 75%) feedwater flow

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1234

Low or high (< -500 mm or +100 mm) steam drum level signals

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1252 Have any of the following signals occurred; 1 out of 3 of the RHS MCPs tripped; Low (< 75%) feedwater flow; Low (< -500 mm) steam drum level; or Low (< 5000 m3/hr) MCP flow?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612520

W1(I) TRIP NUMBER = 1251

1 out of 3 MCP trip, low (< 75%) feedwater flow, or low (< -500 mm) steam drum level

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1241

Low (< 5000 m3/hr) MCP flow

W4(A) LATCH INDICATOR = l

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

The AZ-4 signal is less severe than the FAS, AZ-1, and the AZ-3 CPS signals. Logic is added to prevent a AZ-4 signal if an FAS, AZ-1, or a AZ-3 signal has occurred.

1253 Has either a FAS or AZ-1 signal occurred?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612530

W1(I) TRIP NUMBER = 1131

FAS signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1197

AZ-1 signal

W4(A) LATCH INDICATOR = n

Not latched to allow FAS or AZ-1 to over-ride

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1254 Has either a FAS, AZ-1, or a AZ-3 signal occurred?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612540

W1(I) TRIP NUMBER = 1203

AZ-3 signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 1253

FAS or AZ-1 signal

W4(A) LATCH INDICATOR = n

Not latched to allow FAS or AZ-1 to over-ride

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1255 Have any of the following signals occurred; 1 out of 3 of the RHS MCPs tripped; Low (< 75%) feedwater flow; Low (< -500 mm) steam drum level; Low (< 5000 m3/hr) MCP flow; Manual AZ-4 signal?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612550

W1(I) TRIP NUMBER = 1252

1 out of 3 MCP trip, low (< 75%) feedwater flow, low (< -500 mm) steam drum level, or low (< 5000 m3/hr) MCP flow

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 250

Manual AZ-4 signal

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1256 Have any of the following signals occurred; 1 out of 3 of the RHS MCPs tripped; Low (< 75%) feedwater flow; Low (< -500 mm) steam drum level; Low (< 5000 m3/hr) MCP flow; Manual AZ-4 signal; and no FAS or AZ-1 signal!

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20612560

W1(I) TRIP NUMBER = 1255

1 out of 3 MCP trip, low (< 75%) feedwater flow, low (< -500 mm) steam drum level, or low (< 5000 m3/hr) MCP flow, or manual AZ-4 signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -1254

No FAS, AZ-1, or AZ-3 signals

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

AZ-3 and AZ-4 Power Reduction Logic

The CPS logic for the RBMK-1500 is very complicated and is controlled by a special plant process computer. The AZ-3 and AZ-4 Signals result in a reduction in the core power to 50% or 60% of the nominal power, respectively. A simple PI controller will be used to reduce the reactor power following an AZ-3 or AZ-4 Signal. Reactivity will be added to support a 2%/s power reduction [ ].

The power error signal is generated as follows,

e(t) = ( Pset - Pact )

where,

e(t) power error signal

Pset setpoint for the reactor power

Pact actual reactor power

A proportional-integral control is applied to the error signal as follows,

U = ap {e(t) + 1/t òe(t)dt}

where,

U Reactivity command signal

ap Coefficient of proportionally

Power Signals, Pact

The core power level is evaluated and lagged to eliminate numerical sensitivities.

550 CV-550 = P/P0 = (rktpow 0)/4.2e9 W

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20555000

W1(A) ALPHANUMERIC NAME = power

W2(A) CONTROL COMPONENT TYPE = constant

W3(R) SCALING FACTOR = 1.0

For a constant component, this quantity is the constant value. No additional words are entered on this card, and cards 205CCC01 through 205CCC09 or 205CCCC1 through 205CCCC9 are not entered.

Core power setpoints, Pset

The power setpoint be prescribed to give a 2%/s decrease in power to either 50% of 60%. Trip 1203 (AZ-3)

and Trip 1256 (AZ-4) will be used to signal the actuation of the power decrease logic.

551 CV-551 = 0.5 if the AZ-3 is true and 0.0 if it is false

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20555100

W1(A) ALPHANUMERIC NAME = az-3

W2(A) CONTROL COMPONENT TYPE = tripunit

Specifies a trip unit to convert a trip signal into a control variable.

W3(R) SCALING FACTOR = 0.5

A 0.5 multiplier is used to establish a power run-back to the 50% level.

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20555101

W1(R) TRIP NUMBER = 1203

AZ-3 trip signal

 

552 CV-552 = 0.6 if the AZ-4 signal is true and 0.0 if it is false

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20555200

W1(A) ALPHANUMERIC NAME = az-4

W2(A) CONTROL COMPONENT TYPE = tripunit

Specifies a trip unit to convert a trip signal into a control variable.

W3(R) SCALING FACTOR = 0.6

A 0.6 multiplier is used to establish a power run-back to the 60% level.

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20555201

W1(R) TRIP NUMBER = 1256

AZ-4 trip signal

 

Next determine if a AZ-3 or AZ-4 signal has occurred.

553 CV-553 = 1 if an AZ-3 or AZ-4 signal has occurred or 0 if no signal has occurred.

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20555300

W1(A) ALPHANUMERIC NAME = az-3_4

W2(A) CONTROL COMPONENT TYPE = stdfnctn

Specifies a standard function to evaluate the maximum of two signals

W3(R) SCALING FACTOR = 2.0

A 2.0 multiplier is applied to either the 0.5*AZ-3 or 0.6*AS-4 level. This will generate either 1.0 or 1.2. Since minimum and maximum limits are placed on the output from this control variable, the output is 1.0 if either an AZ-3 or AZ-4 signal has occurred.

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

W6(I) LIMITER CONTROL = 3

3 means both minimum and maximum limits are to be imposed.

W7(R) MINIMUM VALUE = 0.0

W8(R) MAXIMUM VALUE = 1.0

The range of minimum and maximum will allow this control variable to be used as a multiplier to logic that evaluates reactivity addition during an AZ-3 or AZ-4 CPS signal.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Cards 20555301-302

W1(R) FUNCTION = max

Maximum function signal

W2(A) & W3(I) VARIABLE REQUEST CODE V1 = cntrlvar 551

Specifies a AZ-3 signal has occurred.

W4(A) & W5(I) VARIABLE REQUEST CODE V2 = cntrlvar 552

Specifies a AZ-4 signal has occurred.

Next, the 2%/s power decrease is calculated. This requires knowing the current timestep size, dt. dt is not normally available. Consequently, it must be requested as an additional control plot variable. The reduction in power is evaluated as follows,

PsetN+1 = PsetN - 0.02*dt

where,

PsetN+1 New time non-dimensional power setpoint

PsetN Old time non-dimensional power setpoint

CARD 2080XXXX, EXPANDED PLOT VARIABLE REQUEST CARD

Card 20800001

W1(I) & W2(A) EXPANDED VARIABLE REQUEST CODE = dt 0

Requests the timestep size

 

Non-dimensionalize the core power coming out of the reactor physics package as,

554 CV-554 = 0.02 * dt (if AZ-3 or AZ-4 is active) or 0.0 (if no AZ-3 or AZ-4 signal)

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20555400

W1(A) ALPHANUMERIC NAME = delt_p

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier variable.

W3(R) SCALING FACTOR = 0.02

Specifies the gain of 2%/s.

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20555401

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = cntrlvar 553

This variable is set to 1 if an AZ-3 or AZ-4 trip is active or 0 if they are inactive.

W3(A) & W4(I) VARIABLE REQUEST CODE V2 = dt 0

Specifies the timestep size.

 

555 CV-555 = -0.02* Dts

where,

Dts time since the AZ-3 or AZ-4 signal

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20555500

W1(A) ALPHANUMERIC NAME = delt_p

W2(A) CONTROL COMPONENT TYPE = sum

Specifies a sum variable.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20555501-02

W1(R) ADDITIVE CONSTANT = 0.0

No additive constant.

W2(R) GAIN FOR V1 = 1.0

W3(A) & W4(I) VARIABLE REQUEST CODE V1 = cntrlvar 555

This variable is set to 1 if an AZ-3 or AZ-4 trip is active or 0 if they are inactive.

W5(R) GAIN FOR V2 = -1.0

W6(A) & W7(I) VARIABLE REQUEST CODE V2 = cntrlvar 554

Specifies the timestep size times 0.02 if an AZ-3 or AZ-4 trip has occurred. Otherwise, it is zero.

 

556 CV-556 = 1 - 0.02* Dts

where Dts time since the AZ-3 or AZ-4 signal

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20555600

W1(A) ALPHANUMERIC NAME = p_set

W2(A) CONTROL COMPONENT TYPE = sum

Specifies a sum variable.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20555601

W1(R) ADDITIVE CONSTANT = 1.0

The nominal, non-dimensional power (e.g., 1) is subtracted by the 2%/s signal.

W2(R) GAIN FOR V1 = 1.0

W3(A) & W4(I) VARIABLE REQUEST CODE V1 = cntrlvar 555

0.02* Dts, where Dts time since the AZ-3 or AZ-4 signal.

Finally, the power setpoint is calculated. It is limited to 50% and 60% of nominal power for the AZ-3 and AZ-4 signals, respectively.

 

557 CV-557 = max{50% if an AZ-3 signal is active, 60% if an AZ-4 signal is active, and the Power reduction signal (Control variable 556, 1 - 0.02* Dts) }

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20555700

W1(A) ALPHANUMERIC NAME = min_pow

W2(A) CONTROL COMPONENT TYPE = stdfnctn

Specifies a standard function to evaluate the maximum of two signals

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

W6(I) LIMITER CONTROL = 3

3 means both minimum and maximum limits are to be imposed.

W7(R) MINIMUM VALUE = 0.0

W8(R) MAXIMUM VALUE = 1.0

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Cards 20555701-703

W1(R) FUNCTION = max

Maximum function signal

W2(A) & W3(I) VARIABLE REQUEST CODE V1 = cntrlvar 551

Specifies a AZ-3 signal has occurred.

W4(A) & W5(I) VARIABLE REQUEST CODE V2 = cntrlvar 552

Specifies a AZ-4 signal has occurred.

W6(A) & W7(I) VARIABLE REQUEST CODE V2 = cntrlvar 556

Specifies the power reduction signal from an AZ-3 or AZ-4 trip, if present.

Power mismatch signal, e(t)

The power mismatch signal is only generated when either AZ-3 or AZ-4 is true. The difference between the actual non-dimensional power and the setpoint is calculated as follows,

e(t) = ( Pset - Pact ) Power error signal

 

558 CV-558 = e(t) = ( Pset - Pact ) Power error signal

where Pset set power (Control Variable 557)

Pact actual power (Control Variable 550)

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20555800

W1(A) ALPHANUMERIC NAME = error

W2(A) CONTROL COMPONENT TYPE = sum

Specifies a sum variable.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20555801-02

W1(R) ADDITIVE CONSTANT = 0.0

W2(R) GAIN FOR V1 = 1.0

W3(A) & W4(I) VARIABLE REQUEST CODE V1 = cntrlvar 557

Power setpoint

W5(R) GAIN FOR V1 = -1.0

W6(A) & W7(I) VARIABLE REQUEST CODE V1 = cntrlvar 550

Current, non-dimensional reactor power signal

 

The error signal is multiplied by zero if there has not been an AZ-3 or AZ-4 signal.

559 CV-559 = e(t) * 1, if there is an AZ-3 or AZ-4 signal or e(t) * 0, if there is not an AZ-3 or AZ-4 signal

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20555900

W1(A) ALPHANUMERIC NAME = error

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier variable.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20555901

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = cntrlvar 553

This variable is set to 1 if an AZ-3 or AZ-4 trip is active or 0 if they are inactive.

W3(A) & W4(I) VARIABLE REQUEST CODE V2 = cntrlvar 558

Specifies the power error signal.

 

Integral Power Mismatch Signal, 1/t òe(t)dt

The integral of the power mismatch signal is generated next. Separate signals are generated for the LHS TCV and the RHS TCV. The time constant was empirically derived during a manual AZ-3 and AZ-4 scram to give stable response.

556 CV-556 = 1/t òe(t)dt = 1/5 òe(t)dt

where,

t = 5 s time constant

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20556000

W1(A) ALPHANUMERIC NAME = int_err

W2(A) CONTROL COMPONENT TYPE = integral

Specifies an integral variable.

W3(R) SCALING FACTOR = 0.2

Specifies an empirically derived gain of 1/5 s.

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20556001

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = cntrlvar 559

This is the power error signal from Control Variable 559.

 

Reactivity Control Signal

The reactivity control signal is based on combining the proportional and integral error signals.

561 CV-561 = ap { e(t)dt + 1/t òe(t)dt }

where,

ap 20.0 proportional constant derived empirically

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20556100

W1(A) ALPHANUMERIC NAME = p_cont

W2(A) CONTROL COMPONENT TYPE = sum

Specifies a sum variable.

W3(R) SCALING FACTOR = 20.0

An empirically gain of 20.

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Cards 20556101-102

W1(R) ADDITIVE CONSTANT = 0.0

W2(R) GAIN FOR V1 = 1.0

W3(A) & W4(I) VARIABLE REQUEST CODE V1 = cntrlvar 559

Proportional error signal.

W5(R) GAIN FOR V2 = 1.0

W6(A) & W7(I) VARIABLE REQUEST CODE V2 = cntrlvar 560

Integral error signal.

 

In case of a AZ-1 or FAS Signal should occur after a AZ-3 or AZ-4 Signal, the AZ-3 and AZ-4 reactivity signal should be eliminated. A hierarchy is given in the trip logic to allow successively higher scram signals to occur.

562 CV-562 = ap { e(t)dt + 1/t òe(t)dt } * {AZ-3 or AZ-4 Trip Signal}

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20556200

W1(A) ALPHANUMERIC NAME = p_cont

W2(A) CONTROL COMPONENT TYPE = mult

Specifies a multiplier variable.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means no initial value calculation and W4 is used as the initial condition.

CARD 205CCC01, CONTROL COMPONENT DATA CARDS

Card 20556201

W1(A) & W2(I) VARIABLE REQUEST CODE V1 = cntrlvar 561

Proportional-integral reactivity signal.

W3(A) & W4(I) VARIABLE REQUEST CODE V2 = cntrlvar 553

AZ-3 or AZ-4 Signal.