Control system for the RBMK-1500 RELAP5 model


4.8 SDV-A and MSV Control Logic

 

The reactor safety relief valves are installed on a high pressure ring on the main steam piping to protect the reactor from over-pressure conditions. These valves dump into the pressure suppression pools of the ACS. The two ring headers will be modeled together and connected to either end of the steam lines. To simplify the model, the high pressure ring header is not modeled and the MSVs are connected directly to the steam lines. Six MSVs are connected to the LHS of the steam line and 6 MSVs are connected to the RHS. The control logic for opening the MSVs is based on the average pressure at these two locations.

MSV Logic

The pressure setpoints are specified as follows

 

Valve Type

Number of Valves in this Component

Opening Pressure

[MPa]

Closing Pressure

[MPa]

Equivalent Number of Valves

Incremental Non-Dimensional Area

Bank 1 MSV

2

7.4554

7.161

2.00

0.1667

Bank 2 MSV

4

7.5537

7.2594

6.00

0.5000

Bank 3 MSV

6

7.652

7.3575

12.00

1.0000

Total

12

 

 

CARD 205CCC00, CONTROL COMPONENT TYPE CARD

Card 20560000

W1(A) ALPHANUMERIC NAME = p_vid

W2(A) CONTROL COMPONENT TYPE = sum

Specifies a sum component.

W3(R) SCALING FACTOR = 1.0

W4(R) INITIAL VALUE = 6749928.0

Initial conditions established after steady state simulation.

W5(I) INITIAL VALUE FLAG = 0

Zero means non initial value calculation and W4 is used as the initial condition.

CARD 205CCC0X, CONTROL COMPONENT DATA CARDS

Card 20560001

W1(R) ADDITIVE CONSTANT = 0.0

W2(R) GAIN FOR V1 = 0.5

A gain of 0.5 is used to average the LHS and RHS steam line pressures

W3(A) & W4(I) VARIABLE REQUEST CODE V1 = p 100010000

Specifies the LHS steam drum pressure

Card 20560002

W1(R) GAIN FOR V2 = 0.5

A gain of 0.5 is used to average the LHS and RHS steam line pressures

W2(A) & W3(I) VARIABLE REQUEST CODE V2 = p 500010000

Specifies the RHS steam drum pressure

601 CV-601 = MSV Set Points (First Group)

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06010

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 600

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 7.4554e+6

Opening pressure of the first group of MSV

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

602 CV-602 = MSV Set Points (First Group)

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06020

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 600

W3(A) RELATIONSHIP = le

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 7.1613e+6

Closing pressure of the first group of MSV

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

603 CV-603 = 4 Second Delay of Valves Opening

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06030

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = timeof

W5(I) PARAMETER = 601

W6(R) ADDITIVE CONSTANT = 4.0

4 Second Delay of Valves Opening

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

604 CV-604 = 10 Second Delay of Valves Closing

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06040

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = timeof

W5(I) PARAMETER = 602

W6(R) ADDITIVE CONSTANT = 10.0

10 Second Delay of Valves Closing

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 20616000

W1(A) TRIP NUMBER = 602

W2(A) OPERATOR = and

W3(A) TRIP NUMBER = 604

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

First Group of MSV Logic

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616010

W1(A) TRIP NUMBER = 1602

W2(A) OPERATOR = or

W3(A) TRIP NUMBER = 603

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1602 Opening of the first group of MSV.

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616020

W1(A) TRIP NUMBER = 1601

W2(A) OPERATOR = and

W3(A) TRIP NUMBER = -1600

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1603 Closing of the first group of MSV.

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616030

W1(A) TRIP NUMBER = -1602

W2(A) OPERATOR = or

W3(A) TRIP NUMBER = -1602

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

605 CV-605 = MSV Set Points (Second Group)

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06050

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 600

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 7.5537e+6

Opening pressure of the second group of MSV

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

606 CV-606 = MSV Set Points (Second Group)

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06060

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 600

W3(A) RELATIONSHIP = le

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 7.2594e+6

Closing pressure of the second group of MSV

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

607 CV-607 = 4 Second Delay of Valves Opening

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06070

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = timeof

W5(I) PARAMETER = 605

W6(R) ADDITIVE CONSTANT = 4.0

4 Second Delay of Valves Opening

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

608 CV-608 = 10 Second Delay of Valves Closing

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06080

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = timeof

W5(I) PARAMETER = 606

W6(R) ADDITIVE CONSTANT = 10.0

10 Second Delay of Valves Closing

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 20616040

W1(A) TRIP NUMBER = 606

W2(A) OPERATOR = and

W3(A) TRIP NUMBER = 608

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Second Group of MSV Logic

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616050

W1(A) TRIP NUMBER = 1606

W2(A) OPERATOR = or

W3(A) TRIP NUMBER = 607

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1606 Opening of the second group of MSV.

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616060

W1(A) TRIP NUMBER = 1605

W2(A) OPERATOR = and

W3(A) TRIP NUMBER = -1604

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1607 Closing of the second group of MSV.

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616070

W1(A) TRIP NUMBER = -1606

W2(A) OPERATOR = or

W3(A) TRIP NUMBER = -1606

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

609 CV-609 = MSV Set Points (Third Group)

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06090

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 600

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 7.6520e+6

Opening pressure of the third group of MSV

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

610 CV-610 = MSV Set Points (Third Group)

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06100

W1(A) VARIABLE CODE = cntrlvar

W2(I) PARAMETER = 600

W3(A) RELATIONSHIP = le

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the third variable

W6(R) ADDITIVE CONSTANT = 7.3575e+6

Closing pressure of the second group of MSV

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

611 CV-611 = 4 Second Delay of Valves Opening

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06110

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = timeof

W5(I) PARAMETER = 609

W6(R) ADDITIVE CONSTANT = 4.0

4 Second Delay of Valves Opening

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

612 CV-612 = 10 Second Delay of Valves Closing

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 206 06120

W1(A) VARIABLE CODE = time

W2(I) PARAMETER = 0

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = timeof

W5(I) PARAMETER = 610

W6(R) ADDITIVE CONSTANT = 10.0

10 Second Delay of Valves Closing

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

CARD 206CCCC0, CONTROL COMPONENT TYPE CARD

Card 20616080

W1(A) TRIP NUMBER = 610

W2(A) OPERATOR = and

W3(A) TRIP NUMBER = 612

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

Third Group of MSV Logic

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616090

W1(A) TRIP NUMBER = 1610

W2(A) OPERATOR = or

W3(A) TRIP NUMBER = 611

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1610 Opening of the third group of MSV.

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616060

W1(A) TRIP NUMBER = 1609

W2(A) OPERATOR = and

W3(A) TRIP NUMBER = -1608

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1611 Closing of the third group of MSV.

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616110

W1(A) TRIP NUMBER = -1610

W2(A) OPERATOR = or

W3(A) TRIP NUMBER = -1610

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

SDV-A Logic

The 2 SDV-As are modeled with separate valve components with separate control logic. To control the SDV-A steam dump valves, trip control logic will be used. The SDV-A will open at 7.1613 MPa and close at 6.867 MPa. This control logic will be written as follows;

620 Is the steam line pressure greater than 7.161 MPa (Open the LHS SDV-As)?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20606200

W1(A) VARIABLE CODE = p

W2(I) PARAMETER = 175020000

W1(A) and W2(I) represent the steam line pressure at the LHS SDV-As.

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 7.1613e6 Pa

SDV-A pressure setpoint.

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

621 Is the steam line pressure less than 6.867 MPa (Close the LHS SDV-As)?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20606210

W1(A) VARIABLE CODE = p

W2(I) PARAMETER = 175020000

W1(A) and W2(I) represent the steam line pressure at the LHS SDV-As.

W3(A) RELATIONSHIP = le

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 6.867e6 Pa

SDV-A pressure setpoint.

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

625 Is the steam line pressure greater than 7.1613 MPa (Open the RHS SDV-As)?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20606250

W1(A) VARIABLE CODE = p

W2(I) PARAMETER = 575020000

W1(A) and W2(I) represent the steam line pressure at the RHS SDV-As.

W3(A) RELATIONSHIP = ge

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 7.1613e6 Pa

SDV-A pressure setpoint.

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

626 Is the steam line pressure less than 6.867 MPa (Close the RHS SDV-As)?

CARD 206CCCC0, EXPANDED VARIABLE TRIP CARD

Card 20606260

W1(A) VARIABLE CODE = p

W2(I) PARAMETER = 575020000

W1(A) and W2(I) represent the steam line pressure at the RHS SDV-As.

W3(A) RELATIONSHIP = le

W4(A) VARIABLE CODE = null

W5(I) PARAMETER = 0

No comparison value is entered for the second variable

W6(R) ADDITIVE CONSTANT = 6.867e6 Pa

SDV-A pressure setpoint.

W7(A) LATCH INDICATOR = n

W8(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1619 Are the LHS SDVs already open or is the pressure greater than the opening setpoint (7.161 MPa)?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616190

W1(I) TRIP NUMBER = 1621

LHS SDV open signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 620

Above the LHS SDV opening setpoint

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616200

W1(I) TRIP NUMBER = 1619

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -103

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1621 Are the LHS SDVs already open or is the pressure greater than the opening setpoint (7.1613 MPa) and the pressure is not below the closing setpoint pressure?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616210

W1(I) TRIP NUMBER = 1620

LHS SDV open signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -621

The pressure is not below the LHS SDV closing setpoint

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1622 If the LHS SDV-A closed? Note, this trip is required to create a logical opposite of Trip 1621 for the required valve closing trip value in the motor valve input.

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616220

W1(I) TRIP NUMBER = -1621

Inverse of the LHS SDV open signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -1621

Inverse of the LHS SDV open signal

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1624 Are the RHS SDVs already open or is the pressure greater than the opening setpoint (7.1613 MPa)?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616240

W1(I) TRIP NUMBER = 1626

RHS SDV open signal

W2(A) OPERATOR = or

W3(I) TRIP NUMBER = 625

Above the RHS SDV opening setpoint

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616250

W1(I) TRIP NUMBER = 1624

RHS SDV open signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -103

Above the RHS SDV opening setpoint

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

1626 Are the RHS SDVs already open or is the pressure greater than the opening setpoint (7.1613 MPa) and the pressure is not below the closing setpoint pressure?

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616260

W1(I) TRIP NUMBER = 1625

RHS SDV open signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -626

The pressure is not below the RHS SDV closing setpoint

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient

 

1627 If the RHS SDV-A closed? Note, this trip is required to create a logical opposite of Trip 1626 for the required valve closing trip value in the motor valve input.

CARD 206CCCC0, EXPANDED LOGICAL TRIP CARD

Card 20616270

W1(I) TRIP NUMBER = -1626

Inverse of the RHS SDV open signal

W2(A) OPERATOR = and

W3(I) TRIP NUMBER = -1626

Inverse of the RHS SDV open signal

W4(A) LATCH INDICATOR = n

W5(R) TIMEOF QUANTITY (s) = It was set to either true (0.0) or false (-1.0) at the initiation of the transient